Description
Series: CX-WC Series
Type: Barrier Free Restroom Control
Configuration: Barrier Free Components – Controllers
Multi-Function Relay Controller
Brand: Camden
Manufacturer Part Number: CX-EMF-2
Source: Camden Controls product page
Series: CX-WC Series
Type: Barrier Free Restroom Control
Configuration: Barrier Free Components – Controllers
Multi-Function Relay Controller
Brand: Camden
Manufacturer Part Number: CX-EMF-2
Source: Camden Controls product page
| Low-voltage wiring | Required |
|---|---|
| Basis | Structured, independently qualified product connection evidence |
| Preparation | Mount this bare module in a clean, dry protected location such as a metal box, operator header or above a false ceiling; prevent unauthorized access if it is placed on a header. Use double-sided foam tape or the specified mounting screws for this bare module; use the separate cabinet instructions only for a cabinet version. Select the application and bring the required actuator, lock, operator and door-contact wiring to the unit. Make mode and Out2 adjustments with power off; changes require a power reset. Verify actual enclosure clearance because the specification and drawing dimensions differ. |
| Electrical | Supply the CX-EMF-2 with 12/24VAC/DC on P1 terminals1 and2, non-polarized; operating current is 150mA nominal and 500mA maximum. Each selected P3 dry input uses its two-terminal pair. Each P4 Form C output uses COM with NO or NC (two circuit conductors), or COM with both throws (three). Select the mode before assigning input/output functions; these alternatives are not additive. P2 digital/card-reader connections require the actual application diagram and compatible reader. Wire safety devices directly to the operator control box as directed by the manufacturer. A regulated supply is recommended for long-duration washroom strike operation. Field cable runs, type, gauge and shielding require the actual equipment/layout; terminal counts do not specify cable jackets. |
| Electrical wiring required | Yes |
| Conditional connections | CX-EMF-2 operating power P1: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Compatible12/24VAC/DC supply to P1 terminals1 and2; when Installation configuration is Non-polarized operating input; contact ratings are separate from supply requirements.; CX-EMF-2 selected dry input 1: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected external dry contact to P3 terminals1 and2; when Installation configuration is Only when input1 is used by the selected application; function depends on operating mode.; CX-EMF-2 selected dry input 2: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected external dry contact to P3 terminals3 and4; when Installation configuration is Only when input2 is used by the selected application; function depends on operating mode.; CX-EMF-2 selected dry input 3: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected external dry contact to P3 terminals5 and6; when Installation configuration is Only when input3 is used by the selected application; function depends on operating mode.; CX-EMF-2 selected dry input 4: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected external dry contact to P3 terminals7 and8; when Installation configuration is Only when input4 is used by the selected application; function depends on operating mode.; CX-EMF-2 selected dry input 5: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected external dry contact to P3 terminals9 and10; when Installation configuration is Only when input5 is used by the selected application; function depends on operating mode.; CX-EMF-2 selected dry input 6: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected external dry contact to P3 terminals11 and12; when Installation configuration is Only when input6 is used by the selected application; function depends on operating mode.; CX-EMF-2 selected dry input 7: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected external dry contact to P3 terminals13 and14; when Installation configuration is Only when input7 is used by the selected application; function depends on operating mode.; CX-EMF-2 relay1 COM with NO: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals2, 3; when Installation configuration is When relay1 uses NO in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay1 COM with NC: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals2, 1; when Installation configuration is When relay1 uses NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay1 COM with NO and NC: cable runs quantity unspecified; 3 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals2, 3, 1; when Installation configuration is When relay1 uses NO and NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay2 COM with NO: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals5, 6; when Installation configuration is When relay2 uses NO in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay2 COM with NC: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals5, 4; when Installation configuration is When relay2 uses NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay2 COM with NO and NC: cable runs quantity unspecified; 3 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals5, 6, 4; when Installation configuration is When relay2 uses NO and NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay3 COM with NO: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals8, 9; when Installation configuration is When relay3 uses NO in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay3 COM with NC: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals8, 7; when Installation configuration is When relay3 uses NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay3 COM with NO and NC: cable runs quantity unspecified; 3 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals8, 9, 7; when Installation configuration is When relay3 uses NO and NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay4 COM with NO: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals11, 12; when Installation configuration is When relay4 uses NO in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay4 COM with NC: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals11, 10; when Installation configuration is When relay4 uses NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay4 COM with NO and NC: cable runs quantity unspecified; 3 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals11, 12, 10; when Installation configuration is When relay4 uses NO and NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay5 COM with NO: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals14, 15; when Installation configuration is When relay5 uses NO in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay5 COM with NC: cable runs quantity unspecified; 2 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals14, 13; when Installation configuration is When relay5 uses NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 relay5 COM with NO and NC: cable runs quantity unspecified; 3 conductor(s); wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Selected low-voltage controlled circuit to P4 terminals14, 15, 13; when Installation configuration is When relay5 uses NO and NC in the actual operating mode; throw alternatives are not additive.; CX-EMF-2 selected P2 digital interface: cable runs quantity unspecified; conductor count unspecified; wire type not documented; size unspecified; shielding unspecified; rating Field cable type, gauge, shielding and physical cable-run quantities unspecified.; endpoints Compatible reader or selected digital device to P2 digital connector; when Installation configuration is Optional accessory selected: Only for the selected digital/card-reader application; use its full manufacturer diagram and device requirements. |